弱(ruo)電人(ren)弱(ruo)電魂(hun)!今天小編給大家分享(xiang)一篇關于弱(ruo)電機房配(pei)電需要(yao)注意的(de)地(di)方是什么,以及它的(de)要(yao)求。僅供參考(kao)!
機房配電要求:
1)機房供電為(wei)220v 三相五線(xian) 或 三相四(si)線(xian) / 單相三線(xian);
2)機(ji)(ji)房(fang)需配備兩(liang)路(lu)(lu)(lu)不同(tong)(tong)供電(dian)(dian)(dian)局的(de)供電(dian)(dian)(dian),或一路(lu)(lu)(lu)市電(dian)(dian)(dian)、一路(lu)(lu)(lu)發電(dian)(dian)(dian)機(ji)(ji)組(zu)的(de)供電(dian)(dian)(dian),并(bing)配備單獨(du)的(de)配電(dian)(dian)(dian)柜(ju),采用兩(liang)路(lu)(lu)(lu)電(dian)(dian)(dian)同(tong)(tong)時輸入,通過ATS雙電(dian)(dian)(dian)源轉換開(kai)關進行切換,確保(bao)一路(lu)(lu)(lu)電(dian)(dian)(dian)斷開(kai),另一路(lu)(lu)(lu)可以正常(chang)工作(zuo);
3)機(ji)(ji)房(fang)部署一臺(tai)UPS,,滿足市(shi)電(dian)斷開(kai)后,核心機(ji)(ji)房(fang)設備能(neng)夠正常運(yun)行2小時;(具體電(dian)池(chi)容量(liang)及輸(shu)出功率煩請(qing)供應商評估)
4)每個機(ji)柜配(pei)(pei)兩路PDU,每路PDU有(you)12插口,一路PDU接市(shi)電(dian),一路PDU接UPS電(dian),并在(zai)配(pei)(pei)電(dian)柜配(pei)(pei)有(you)獨(du)立的控制開關;
5)機房照明(ming)及墻面檢(jian)修插(cha)座均采用一(yi)路市電(dian)、一(yi)路UPS供電(dian);
6)機房需安裝應急燈,要求停電開啟/關燈開啟;
7)確認機房電(dian)路是否能接入(ru)物業應急(ji)柴油(you)發電(dian)組,確保(bao)市(shi)電(dian)中斷后,核心機房設備能保(bao)障(zhang)正常供電(dian)。