弱電(dian)人弱電(dian)魂!今天小編(bian)給大家(jia)分(fen)享(xiang)一篇(pian)關于弱電(dian)機(ji)房配電(dian)需要注意的(de)(de)地方是(shi)什(shen)么,以(yi)及(ji)它的(de)(de)要求。僅供參考!
機房配電要求:
1)機房(fang)供電為(wei)220v 三(san)相五(wu)線 或 三(san)相四(si)線 / 單相三(san)線;
2)機房需配備兩(liang)路(lu)(lu)不同供(gong)(gong)(gong)電(dian)(dian)局的供(gong)(gong)(gong)電(dian)(dian),或一路(lu)(lu)市電(dian)(dian)、一路(lu)(lu)發電(dian)(dian)機組(zu)的供(gong)(gong)(gong)電(dian)(dian),并配備單(dan)獨的配電(dian)(dian)柜,采(cai)用兩(liang)路(lu)(lu)電(dian)(dian)同時(shi)輸入,通過ATS雙電(dian)(dian)源轉換開關進行切換,確保一路(lu)(lu)電(dian)(dian)斷(duan)開,另一路(lu)(lu)可以正常(chang)工作;
3)機房部署一臺UPS,,滿(man)足市電斷(duan)開(kai)后,核心(xin)機房設備能夠正常運行(xing)2小時;(具體電池(chi)容量(liang)及輸出(chu)功率(lv)煩請供應(ying)商評估(gu))
4)每個(ge)機柜(ju)配(pei)兩路PDU,每路PDU有12插口,一(yi)路PDU接市電(dian),一(yi)路PDU接UPS電(dian),并(bing)在(zai)配(pei)電(dian)柜(ju)配(pei)有獨立(li)的控制開關;
5)機房照明及墻面(mian)檢(jian)修插座均采用一路市電、一路UPS供電;
6)機房需安(an)裝應急燈,要(yao)求停電開(kai)啟(qi)/關燈開(kai)啟(qi);
7)確(que)認機房電路是否(fou)能(neng)接入物(wu)業應急柴油發電組(zu),確(que)保市電中(zhong)斷(duan)后,核心機房設備能(neng)保障正(zheng)常(chang)供電。